Many chemical and oilfield blending plants handle flammable solvents. Where vapour from those solvents can mix with air, the plant is a hazardous area, and every motor, instrument and light in it must be suitable for that area. This guide explains where the vapour comes from, how areas are classified, and what that means for the agitators and the rest of the equipment. It is a planning guide: the classification of a real plant is done by the owner or its safety consultant, under the rules that apply at the site.
Where flammable vapour comes from
In a blending plant, vapour is released wherever solvent is open to air or displaced from a tank:
- charging points, manholes and hatches when they are opened;
- tank vents, as tanks are filled and as they breathe with temperature;
- drum and IBC filling, where vapour is pushed out of the container;
- tanker unloading connections;
- pump and agitator seals, valve glands and flanges, as small leaks.
The flash point of each solvent and product decides how readily it gives off flammable vapour at the site temperature. A product that is safe in a cool climate can be above its flash point in a Gulf summer.
How areas are classified
Most of the world uses zones. Zone 0 is where a flammable atmosphere is present continuously or for long periods, typically inside tanks above the liquid. Zone 1 is where it is likely in normal operation, such as around open charging points and vents. Zone 2 is where it is not likely, and short-lived if it occurs, such as around flanges and seals. The classification also records the gas group and temperature class of the substances, which limit the equipment that can be used. Some regions use the older class and division system, which maps onto the same ideas.
What it means for agitators
- Motor. A motor protected for the zone, gas group and temperature class, usually flameproof. Where electric drives are not allowed, an air motor drives the agitator.
- Seal. A closed tank with a mechanical seal on the shaft, so that vapour does not escape at the agitator; a double mechanical seal with a barrier fluid where no release to atmosphere is acceptable.
- Surface temperature. Bearings, gearboxes and seals must stay below the temperature class of the vapour.
- Static and earthing. Shaft, tank and drive bonded and earthed, so static charge from the moving liquid cannot build up.
The rest of the plant
- Instruments, junction boxes, lighting and control stations suitable for the zone; control panels placed outside the hazardous area where possible.
- Tank vents routed to a safe location, with flame arrestors where needed; nitrogen blanketing for tanks where it is specified.
- Earthing and bonding of tanks, piping, drums, IBCs and tankers during transfer.
- Closed charging and filling, to reduce the size of the zones.
- A layout that keeps ignition sources, such as the electrical room, boiler and workshop, outside the zones and upwind.
Design it in from the start
Hazardous-area requirements change motors, instruments, layout and cost, so they belong at the start of the design, not at the end. Tell us the solvents and products, the site and its classification practice, and we will design the agitators and the plant equipment to suit. See oilfield chemical blending plants, or read what each oilfield chemical needs from the plant.